Proportional Purging Gas Valve for Ex px Operating Equipment

05-0056-00..

Certificates

German English PTB 00 ATEX 2202 X
English IECEx PTB 13.0011X

Ex protection type

ATEX:
Ex II 2G Ex m II T4
IECEx:
Ex m II T4

Ambient temperature

-10 °C to +60 °C

Description

The proportional purging gas valve activated by the APEX control unit conducts the supplied purging gas into the Ex px control cabinet.

During the purging phase the purging gas valve opens far enough to allow the max. purging gas pressure to be reached and accordingly ensures purging pressure in the encapsulated control cabinet.

After the purging phase the purging gas valve closes. The leakage from the Ex px control cabinet is compensated by the linear opening of the valve. Only the actual loss by leakage is compensated when the purging gas valve is used.

Technical data (extract)

(Click here for more information)
Protection classIP 65
Dimensionssee data sheet
Max. Ex px control cabinet capacity: 1,000 litres
Pressure0 to 4 bar
Weightapprox. 1.2 kg
VoltageAC 230 V/15 W/50 to 60 Hz
AC 115 V/15 W/50 to 60 Hz
ConnectionValve connection: G 3/8"
Nominal diameter: 6.0 mm

Documentation

Data Sheet - Proportional Purging Gas Valve for Ex px Operating Equipment German English French Russian Spanish Portuguese Italian 
Declaration of Conformity 2834-* PD33 German English French 
Customer requirements - Ex p equipment German English French Russian Spanish Portuguese Italian 
Operating Instructions - Proportional Purging Gas Valve for Ex px Operating Equipment German English