Ex Closed Loop Chiller FKS-KWS
Ex kaitse liik
II 2G Ex de [ia] II C T4 (control unit)
Optional available classification:
Ex px mb de IIC T3 or T4 (chiller)
Ex de [ia] IIC T4 (control unit)
Class I, Division 2, Groups B, C and D
AEx px mb de IIC T3 or T4 (chiller)
Ex de [ia] IIC T4 (control unit)
Class I, Zone 1, Gas Group IIC
Class I, Division 2, Groups B, C and D
Ümbritseva keskkonna temperatuur
Option: -20 to 55 °C (-4 to 131 °F)
alternative temperature on request
Kirjeldus
The BARTEC BENKE closed loop chillers consist of an air-cooled high performance condenser combined with an encapsulated compressor and are suitable for the installation in explosive gas atmospheres defined as zone 1. The electrical control system is supplied with its own Ex d housing. Optionally, with a BARTEC BENKE analyzer, the control system can be placed inside the Ex p housing of the analyzer.Problems on site where utilities supplying cooling water is of a lower quality or special requirements of cooling water are needed, BARTEC BENKE closed loop chillers can be supplied to meet these applications. The chillers can be supplied with diverse refrigerating capacities which allow the chillers to be used on single analyzers up to complete analyzer houses, peltier elements and heat exchangers. They can be supplied suitable for indoor or outdoor use. Depending on the flow rate required, different pump capacities are also available.
Tehnilised andmed (väljavõte)
(Täpsema info jaoks klikka siia)Protection class | IP 54 (electrical)/NEMA 7 (NEMA 12 and NEMA 3 on request) |
Dimensions | FKS 0.5-KWS: 500 x 960 x 530 mm FKS 1.4-KWS: 500 x 960 x 530 mm FKS 2.4-KWS: 600 x 960 x 530 mm FKS 4-KWS: 1200 x 1100 x 600 mm FKS 6-KWS: 1200 x 1100 x 700 mm FKS 10-KWS: 1200 x 1100 x 700 mm |
Weight | FKS 0.5-KWS: 150 kg FKS 1.4-KWS: 150 kg FKS 2.4-KWS: 160 kg FKS 4-KWS: 260 kg FKS 6-KWS: 290 kg FKS 10-KWS: 310 kg |
Refrigerant | R134a or R404 |
Pipe fittings | FKS 0.5-KWS ? FKS 2.4-KWS: ? " NPT FKS 4-KWS ? FKS 10-KWS: depending on application |
Effective cooling capacity | FKS 0.5-KWS: typical 500 W at -35 ?C (-31 ?F) FKS 1.4-KWS: typical 1.4 kW at 10 ?C (50 ?F) FKS 2.4-KWS: typical 2.4 kW at 10 ?C (50 ?F) FKS 4-KWS: typical 4 kW at 10 ?C (50 ?F) FKS 6-KWS: typical 6 kW at 10 ?C (50 ?F) FKS 10-KWS: typical 10 kW at 10 ?C (50 ?F) |
Voltage | FKS 0.5-KWS ? FKS 1.4-KWS: 1 phs. AC 230 V or 3 phs. AC 400 V 50Hz/AC 440 V 60Hz other ratings on request FKS 1.4-KWS ? FKS 10-KWS: 3 phs. AC 400 V 50Hz/AC 440 V 60Hz other ratings on request |
Power | FKS 0.5-KWS 1.8 kW FKS 1.4-KWS 1.8 kW FKS 2.4-KWS 2.3 kW FKS 4-KWS 3.2 kW FKS 6-KWS 4.3 kW FKS 10-KWS 6.5 kW |
Connection | M25 mains supply, M20 fault message or conduit |