PROFIBUS-Interface 16 x digital out Ex i

07-7331-2301/1.00

Features

  • 16 channels
  • Direct control of solenoid valves
  • Galvanic isolation
  • LED display
  • EMC according to
    DIN EN 61000-4-2: 2001,
    DIN EN 61000-4-3: 2008,
    DIN EN 61000-4-4: 2003,
    DIN EN 61000-4-6: 2007
  • Programmable address on front panel

Certificates

German English PTB 97 ATEX 1066 U
German English TUEV 00 ATEX 1649
English IECEx PTB 11.0082U
English IECEx TUN 11.0035X
English CSA 2484303
Russian GOST R POCC DE.ME92.B02630
Kazakh GOST-K-KZ4710193.01.01.00142
Byelorussian GOSPROMNADZOR 11-02-0015-2012
English Portuguese UL-BR 13.0397U
English Portuguese UL-BR 13.0669X

Ex protection type

Ex II 2 (1) G / I M 2
Ex d e [ib] IIC/IIB Gb
Ex d e [ib] I Mb
Class I Zone 1 IIC
A/Ex d e [ib] IIC Gb

Ambient temperature

Directive 2004/108/EC
Directive 94/9/EC

Description

This module is used for the control of intrinsically safe actuators in the Ex area via PROFIBUS-DP.

It is, for example, possible to directly connect intrinsically safe solenoid valves or indicator lights.

LEDs on the front of the module output bus status as well as output states.

Technical data (extract)

(Click here for more information)
Protection classModule: IP 66
Terminals: IP 20
Terminals with cover: IP 30
StructureFlameproof, clip-on enclosure for TH 35 rail
Dimensionssee data sheet
MaterialHigh-quality thermoplastic
Storage temperature-40 ?C to +60 ?C
Weight2.1 kg
DisplayLEDs on front panel
Status: ON, BF, SF, U2
Outputs: LED yellow, active; LED red, short-circuit
VoltageSupply voltage (L+, L-, U+, U-): DC 20 V to DC 30 V
Output voltageDC 18.1 V (at U+ ≥ 22 V)
Output powerP = 2.5 W (L+, L-)
P = 15 W (max.) (U+, U-)
Power dissipation8 W
Bus interfaceRS 485 with screw-clamping terminals
Galvanic isolationL+, L-//Bus//U+, U-, outputs
Connection2.5 mm?, fine stranded

Documentation

Data Sheet - PROFIBUS-Interface 16 x digital out Ex i German English French Russian 
Declaration of Conformity 01-7331-7C0012 German English French