Remote I/O Module ANTARES 4AIOH
17-6143-1007/0000
Features
- 4 channels analog in/out
HART Ex ia IIC - 4 channels freely configurable as
In or Out - Inputs active or passive
- 2-, 3-, 4-conductor technology
- Integrated bus rail
- Installation in ATEX Zone 1/2
or Zone 21/22 - Hot-Swap
- Galvanic isolation between the
- inputs/outputs and the system
- Line break/short-circuit monitoring
- Plug-in and codable spring clamps
Certificates
IECEx PTB 11.0061
DNV A-13339
GOST R POCC DE.ME92.B02833
RTN PPC 00-049813
KTL 13-KB4BO-0302
KTL 13-KB4BO-0303
UL BR 13.0260
Ex protection type
II 2 (1)G Ex ib [ia IIC/IIB Ga] IIC T4 Gb
II (1)D [Ex ia Da] IIIC
IECEx:
Ex ib [ia IIC/IIB Ga] IIC T4 Gb
[Ex ia Da] IIIC
Ambient temperature
EN 61241-0:2006 EN 61241-11:2006
EN 61000-6-2:2005 EN 61000-6-4:2007
EN 55011:2007
IEC 60079-0:2007
IEC 60079-11:2006
IEC 61241-0:2004,
modifiziert + Corr. Nov. 2005
IEC 61241-11:2005 + Corr. Feb. 2006
Description
The Remote I/O Module ANTARES 4AIOH is operated and supplied with power by means of the Rail Control Unit (RCU) ANTARES. This module allows the direct linking of 4 intrinsically safe 2-, 3-, 4-conductor transmitters or the output of 0 up to 20 mA or 4 up to 20 mA signals.The hot-swap capability allows the electronic unit to be replaced without disconnecting from voltage even in an Ex atmosphere. The internal and galvanically isolated bus connection is established by simply joining the modules to the RCU. A bus rail is not necessary. Line break/short-circuit monitoring can be programmed for each channel. The bus status messages and individual messages per channel are displayed through the LEDs. This facilitates diagnosis at the module as well. The ANTARES Designer software allows parameters to be set for the signal range, channel type (in or out), HART function through DTM and a 4-stage input filter for each channel. See the system description for installation instructions.
Technical data (extract)
(Click here for more information)Protection class | (EN 60529) Enclosure: IP 30 in the ANTARES system construction |
Dimensions | (W x H x D) 22.5 mm x 110 mm x 114.5 mm |
Material | Enclosure material: PA |
Installation | Mounting rail TH 35-15 EN 60715 (Metal) |
Storage temperature | -25 ?C up to +85 ?C |
Humidity | 5 up to 95 %, non-condensing |
Vibration | (EN 60068-2-6) 2 g/7 mm; 3 Hz up to 200 Hz in all 3 axes |
Shock | (EN 60068-2-27) 15 g, 11 ms in all 3 axes |
Weight | approx. 390 g |
Display | LEDs in enclosure front: Status ST, PWR, ERR1, ERR2 Inputs/ 2 LEDs per channel Outputs 1 x LED yellow channel setting 1 x LED red channel error |
Interface | Number of channels 4 inputs or outputs Ex i (short-circuit-proof) Inputs active/passive |
Voltage | Supply voltage: through internal bus |
Resistance | Input resistance: Ri = 50 Ohm |
Connection | - plug-in tension spring clamp 4-pole - up to 2.5 mm? - optional coding and numbering |