RLW Monitoring Electronics with Locating

17-85G1-2.2.

Features

  • System status with plain text report
  • Quick and precise localisation of the leakage location
  • Monitoring lengths to 3.000 m
  • No system calibration required
  • Simple integration into the building surveillance
  • With combinable sensor cable and point sensor

Certificates

0 ?C to +50 ?C

Description

The RLW monitoring electronics can be easily integrated into the building surveillance. System calibration is not necessary. To safeguard the system, the software is password-protected. RLW can be combined both with the sensor cable and also with the point sensor.

The system status appears as a plain text report. The menu texts in the display are stored in 3 languages, German, English and French.

The front membrane texts are in three languages as standard.

The location of the leakage appears in the display quickly and precisely. This ensures that the location of the leakage can be found rapidly and countermeasures introduced immediately. The max. monitoring length is 3.000 m and can be displayed in metres or feet. For each measuring channel up to 1.500 m of sensor cable can be connected. The monitoring length can be divided into 50 zones per measuring channel.

Technical data (extract)

(Click here for more information)
Protection classIP 65
Structureplastic wall-mounted enclosure with transparent protective cover, terminal connection chamber and cable glands
Dimensions284 x 217 x 143 mm (W x H x D); (dimension H without cable glands)
Displayoptical: LED displays; operation/leakage/rupture/fault
acoustic: piezoelectric buzzer (can be switched on and off)
InterfaceRS 232 interface (standard) and RS 485 (options) block-oriented, secured single-master protocol for connecting to the building services management
Keyboardmembrane keyboard
operation of all functions including the plain text inputs
Memorystorage of the last 20 events with date, time and plain text
ConnectionInputs:
- voltage supply (standard) AC 230 V or AC 115 V/50 to 60 Hz/8VA or DC 12V or DC 24V/7W
- sensor connection

Outputs:
- two floating change-over contacts for leakage report: per measuring channel (3 A at AC 230 V)
- two floating change-over contacts for fault (fail-safe) power failure surveillance: 3 A at AC 230 V

Documentation

Data Sheet - RLW Monitoring Electronics with Locating German English French Russian