DEPU Complete Digital Solution

17-8887-2636/2300

Features

  • Complete solution for tubular steam trace heaters-controllers, limiters and power setpoint adjusters all in one unit
  • Alteration of adjusting parameters also possible in potentially explosive areas
  • Current carrying capacity 25 A
  • Fault-free full wave control
  • Sensor input, intrinsically safe
  • Allows easy output adaptation to heating circuit changes

Certificates

German English TUEV 03 ATEX 2088
Russian GOST R POCC DE.ME92.B02498
Byelorussian GOSPROMNADZOR 11-02-0015-2012

Ex protection type

Ex II 2G EEx m e ib [ib] IIC T4

Ambient temperature

EN 50020, EN 50019,
EN 50028, EN 50014
Directive 94/9/EC
NAMUR NE 21

Description

A complete solution for DEPU tubular steam trace heaters is provided by temperature control, limitation and power setpoint adjustment, all in one unit. DEPU is ATEX-certified and approved for use in potentially explosive areas.

Structure

All functional units are integrated in a standard casing of aluminium. The connecting lines up to 6 mm? are contacted with cage tension spring clamps.

Function

The controller is designed as a two point controller and measures the temperature by means of a Pt 100. The limiter works as an independent system and measures the temperature at the hot spot with ist own Pt 100. If the temperature exceeds the limit value the limiter interrupts the heater permanently and a fault signal is given. All fault alarms are indicated by a master fault contact. Resetting can be carried out directly on the unit or externally with a key. The power setpoint adjuster works as a fault-free full wave control by means of a semi-conductor relay. A 7-segment display guarantees good readability of the temperature values of controller and limiter through the viewing plate.

Technical data (extract)

(Click here for more information)
Protection classIP 65
Dimensionssee data sheet
MaterialStandard enclosure of aluminium, grey
Storage temperature-30 ?C to +70 ?C
Weight6 kg
Temperature range0 ?C to +450 ?C (electronic)
VoltageAC 230 V +10%/-15 % (50 to 60 Hz)
(special voltage 254 V on request)
Currentmax. 25 A (power setpoint adjuster)
Powerno load: 11 VA
full load: 5.7 kVA
ConnectionTerminals: Wago cage clamp
Mains supply line 1 x M25 (M32 opt.)
Heating cable/cold end 1 x M20
Fault alarm 1 x M20
Remote reset 1 x M20
Sensor 2 x M16

Documentation

Data Sheet - DEPU Complete Digital Solution ? Controllers-Limiters-Power Setpoint