DTL III Ex Digital Safety Temperature Limiter
17-8865-4.22/22003000
Features
- ATEX approval
- Optimised for trace heating applications (with service entry)
- Wide-range voltage input
- Sensor surveillance
- In conjunction with Pt100 Ex, it can be used for monitoring temperature in explosion-proof heating circuits
Ex protection type
Ambient temperature
Description
The new DTL III Ex digital temperature limiter, which is adapted to (trace) heating applications, serves to monitor heating and heating circuits. The device is installed in the non-hazardous area. The heating or heating circuits can be installed both in media-protected and also in hazardous areas. Thanks to their integrated power supply unit with wide-range voltage, the devices can be used almost everywhere in the world.Function
If the temperature at the Pt 100 exceeds the set limit value, the DTL II Ex permanently interrupts the normally closed 16 A switch contact. This situation is detected by a volt-free alarm contact (change-over contact) and passes on the signal to the control panel. After a temperature drop of 5 K below the limit set point, or after a fault has been remedied, the limiter can be re-activated by means of a re-set button on the device itself or via a remote re-set control. The DTL will also interrupt the switch contact in the event of a sensor open or short circuit. Process reliability is increased by additional monitoring functions such as supply voltage monitoring, pre-alarm, measuring circuit monitoring for sensor break, interruption and short-circuit as well as undershooting/overshooting of the measuring range. A multi-stage password management is available for effective parameter protection. When doing service work on the heating circuit, the load output can be turned off by means of a digital input and the temperature alarms can be disabled. Using the programming interface, the device parameters can be read out with a programming key and transmitted to other devices.Technical data (extract)
(Click here for more information)Protection class | II |
Dimensions | 84 mm x 70 mm x 60 mm (Length x Width x Depth) |
Weight | 0.2 kg |
Measurement range | -200 ?C to +850 ?C |
Sensitivity | (? 0.5% of the actual level or ?1?C;the higher level applies)?1 digit |
Voltage | see data sheet |
Current | see data sheet |
Power | Max. 4 VA |
Electrical life | relay outputs: at least 100,000 switching cycles |