EMK Heating Circuits, Factory Terminated, Standard, Ex

27-361.-.../..

Features

  • All necessary connection components in one kit
  • Easy assembly of the necessary components
  • Wide variety to choose from
  • Ready assembled, quick to install
  • High quality factory terminated assemblies

Certificates

German English PTB 08 ATEX 1064
German English PTB 99 ATEX 1080 U
German English Sira 05ATEX3008X
English DNV E-10451
Russian TC RU C-DE.GB06.B.00230
Kazakh GOST-K-KZ4710193.01.01.00139
Ukrainian No. 905
Byelorussian GOSPROMNADZOR 11-02-0015-2012

Ex protection type

Ex junction box:
Ex II 2GD Ex e II T6
Hot to cold connection sleeve:
Ex II 2G EEx e II

Description

These connection kits have been specifically designed for EMK heating cables and their particular fields of application.

There are two versions of the EMK connection kit available:
  • Standard version
  • Ex version
    for use in Ex areas

The EMK connection kits consist of:
  • Cold leads
    in the required quantity
  • Hot to cold joints
    in the required quantity
  • Pre-cut and factory terminated assembly of the cold leads and hot to cold joints with EMK heating cable (heating cables must be ordered separately. See ordering information).

Technical data (extract)

(Click here for more information)
Protection classGrey enclosure: IP 65, Cable gland IP 54 up to IP 65
Black enclosure: IP 65, Cable gland IP 65
Hot to cold connection sleeve: IP 68
Dimensionssee data sheet
Cold leads Standard length: 1.2 m, Outer diameter: 5.3 mm
Hot to cold connection sleeve: L = 35 mm, ? = 10 mm
MaterialEnclosure: Polyester, glass-fibre reinforced
Colour grey, similar to RAL 7001, Surface resistance > 1012
Colour black, RAL 9005, Surface resistance < 109

Cold leads: copper
Hot to cold connection sleeve: S/S 1.4401
Voltageup to 415 V
Connectionsee data sheet

Documentation

Data Sheet - EMK Heating Circuits, Factory Terminated, Standard, Ex German English French Russian