HTSB system - Cold-applied technologywith brass cable gland, explosion protected

05-0091-0150

Funktsioonid

  • Direct connection of self-limiting heating cable into the junction box
  • Connection and termination in one set
  • Small place saving and economic solution
  • Easy project and assembling with silicone cold applied technology

Sertifikaadid

English Sira 10ATEX3268
English Sira 01ATEX1270X

Ex kaitse liik

Heating cable and silicone parts:
Ex II 2GD IP 6X
Ex e IIC T2 Gb
Ex t IIIC T300 °C Db
Cable gland:
Ex II 2GD
Ex e II
Ex tD A21 IP 68

Ümbritseva keskkonna temperatuur

Ambient temperature range depends on used junction box: -40 °C to +180 °C
Permissible ambient temperature
for heating cable switched on: -40 °C to +180 °C
for heating cable switched off: -40 °C to +180 °C

Kirjeldus

When an enclosure is connected directly, the heating tape (Type no. 07-5819-...2) is first stripped and then a silicone hose wetted with adhesive is pushed over the supply line. A green/yellow protective hose is pulled on over the braiding.

The braiding and the brass cable gland is to be prepared for connection to protective earth. Likewise after stripping the end of the tape, a silicone cap wetted with adhesive is put on it. The adhesive is completely set hard after 24 h and room temperature in the ambient cure time. The heating cable can be mounted after a hardening time of 15 min. tack-free time.

Tehnilised andmed (väljavõte)

(Täpsema info jaoks klikka siia)
VoltageAC 110 V to AC 120 V
AV 220 V to AC 277 V
PowerNominal power output: 15 W/m to 90 W/m

Dokumentatsioon

Data Sheet - HTSB system - Cold-applied technology German English French Russian 
Operating Instructions - Connection and remote termination for heating circuit HTSB Ex German English French Russian