HSB System - Junction Boxes for Heat Shrink Technology

07-5103-91..

Certificates

German English PTB 08 ATEX 1064
German English IBExU00ATEX1081
English DNV E-10451

Ex protection type

Ex II 2G Ex II T6 or T5
Ex II 2D Ex tD A21 IP 6x T 95 °C
Ex II 2D Ex tD A21 IP 6x T 80 °C

Ambient temperature

EPDM: -20 °C up to +100 °C
Silicone: -55 °C up to +100 °C

Description

Junction boxes are used to connect one or more heating circuits to the power supply.

Polyester enclosures are available with the necessary cable glands and threaded cable entries.

Aluminium junction boxes are available upon request.

Technical data (extract)

(Click here for more information)
Protection classCover gasket: IP 65
Cable gland for power supply cables: IP 67
Dimensionssee data sheet
Materialpolyester, glass-fibre reinforced
Voltagemax. AC 254 V
ConnectionSupply cable, cross section 2.5 mm? up to 6.0 mm?

Documentation