Bushing conductor studs 690, 1000 and 1600 Volt

T0S8....A....V-..

Features

  • 16 A to 630 A
  • 690 V, 1000 V and 1600 V
  • Max. ambient temperature 130

Certificates

German English PTB 04 ATEX 1099 U

Ex protection type

Ex II 2G Ex de IIC Gb
Ex I M2 Ex de I Mb

Ambient temperature

-30 °C up to +130°C

Description

A bushing conductor stud is a component with which the electrical connection between an enclosure in type of protection ?Flameproof enclosure d? and its connection enclosure in type of protection ?Increased Safety e? is established. The cable bushing includes a threaded metal sleeve, a ceramic insulation, terminals and a stud. Standard threaded sleeves from M16 to M42 are included in the delivery of bushing conductor studs.

The diameter of the stud depends on current and the terminal size on the cable diameter. Thanks to different types of terminals, vertical as well as horizontal cable connection is possible. Special terminals are available on request. After installation, the bushing conductor stud needs to be secured by means of a nut or adhesive to prevent self-loosening.

Technical data (extract)

(Click here for more information)
Protection classEN 60079-0: 2007; EN 60079-1: 2007
Dimensionssee data sheet
MaterialInsulation ceramic: C610
Stud:
16 A to 250 A: CuZn39Pb2
400 A to 630 A: E-Cu
InstallationM16 x 1.5 to M42 x 1.5
Voltage690 V, 1000 V and 1600 V
Current16 A to 630 A (see data sheet)
Connection1,5 mm? to 300 mm?

Documentation

Data Sheet - Bushing conductor studs 690, 1000 and 1600 Volt German English French Russian Spanish 
Customer requirements - Cable entries/line bushings German English French Russian