Polyester distribution boxes for Zone 1 and Zone 21, black
Certificates
IECEx PTB 09.0009X
CSA 2557738
TC RU C-SI.GB08.B.00308
No. 912
GOSPROMNADZOR 11-02-0015-2012
T?V 13.1193 X
09-AV4BO-0403X
CCEs P250922/.
Ex protection type
II 2G Ex ia IIC T6, T5
II 2D Ex tD A21 IP6x T 80 °C
Ambient temperature
-20 °C (-55 °C) up to +55 °C bei T5
Description
Polyester distribution boxes have been of great advantage in many industrial plants. They offer safe protection even when they are exposed to extreme environmental conditions, aggressive chemical media or high mechanical stress.The narrow sides within the enclosure hold threaded bushings for the fixing of terminal rails or mounting panels. The enclosure is mounted by means of insulated screws outside of the lid sealing gasket.
These black high-quality explosion-proofed enclosures are used in hazardous areas by inflammable dust (Zone 21 and 22).The fundamental prerequisites of the ?protection through enclosure? protection class are fulfilled with the heating up calculation as per the accompanying sheet and a separate IP protection test. EC model test certification was issued in 2000 by the nominated body IBExU.
Technical data (extract)
(Click here for more information)Protection class | IP 66 (EN 60529/IEC 60529) |
Dimensions | see data sheet |
Material | glass-fiber reinforced polyester, EN 60079-0 halogen-free, RAL 9005, black |
Voltage | Rated voltage max. 1 100 V |
Resistance | surface resistance < 109 Ω |
Documentation
Declaration of Conformity Type 07-5103, 07-5105, 07-5106, 07-5107
Customer requirements - Terminal Boxes
Operating Instructions - Distribution box 07-5103, 07-5105, 07-5106, 07-5107