Digital Purging Gas Valve for Ex pz Operating Equipment

03-5110-00..

Certificates

Ex II 3G Ex nA T4

Ex protection type

-10 °C to +40 °C

Description

The digital purging gas valve controlled by the SILAS controller conducts the supplied purging gas into the Ex pz control cabinet.

During the purging phase the purging gas valve opens and consequently provides purging pressure in the encapsulated control cabinet.

After the purging phase the purging gas valve closes. The leakage from the Ex pz control cabinet is compensated by an integrated adjustable leakage air valve.

Technical data (extract)

(Click here for more information)
Protection classIP 65 with fitted connector
Dimensionssee data sheet
Pressure0 to 4 bar
Weightapprox. 1.2 kg
VoltageAC 230 V/6.5 VA/50 to 60 Hz
AC 115 V/5.6 VA/50 to 60 Hz
DC 24 V/6.0 W
Voltage tolerance: ? 10%
ConnectionValve connection: G 3/8?
Nominal diameter: 6.0 mm
Control cabinet borehole: 17 mm

Documentation

Data Sheet - Digital Purging Gas Valve for Ex pz Operating Equipment German English French Russian Spanish Portuguese Italian 
Declaration of Conformity Type 03-5110-00** German English French 
Operating Instructions - Digital Purging Gas Valve for Ex pz Operating Equipment German English French Russian Spanish Portuguese Italian