Motor Purge Control System MPCfor Zone 1 and 2
.7-3711-6.10/.M.0
Features
- Automatically functioning Ex px purge system for electric motors
- Fail-safe control
Certificates
IECEx BVS 13.0039
NEPSI GYJ13.1200
CSA 2654548
KTL 13-KB4BO-0634
NCC 14.02972 X
Ex protection type
II 2(1)G Ex de [ia Ga px] IIC T4 Gb
Zone1, IECEx:
Ex de [ia Ga px] IIC T4 Gb
Zone 2, ATEX:
II 3G Ex nA nC [ic pz] IIC T4 Gc
Ambient temperature
94/9/EC
Description
Motor Purge Control System consisting of a Motor Purge Controller - MPC and a Motor Purge Valve - MPV (outlet valve) is a unit allowing a safe operation of electric motors in a hazardous environment.The explosion protection is ensured by means of a pressurised enclosure with leakage loss compensation. The Motor Purge Control System monitors, controls and regulates the purging gas supply for the Ex p motor.
Any malfunctioning in the system or the purging gas supply will be reported reliably and deactivated by safely isolating the Ex p motor.
Technical data (extract)
(Click here for more information)Protection class | IP 55 (internal components IP 65) |
Structure | inside the protective housing |
Dimensions | see data sheet |
Material | Enclosure material: sheet steel (stainless steel on request) Varnish: RAL 7035 |
Pressure | Pressure measuring range: 0 to 25 mbar |
Purging time | Purge time: 0 to 99 minutes (settable) |
Pipe fittings | Supply of purge gas Inlet: R 1" internal thread MPC S2 R 1?" internal thread MPC S3 Outlet: R 1" internal thread Signal lines: 3 x pipe connection 10 mm |
Voltage | AC 230 V (AC 115 V) ? 10 % |
Power | P = approx. 20 W/AC 230 V |
Connection | Connection terminals: 2.5 mm? |