Ex p control unit APEX 2003.SI (Dilution)

07-3711-4213/.001

Features

  • 4 voltage free contacts
  • 3-line LCD display
  • LED status display
  • Modular design
  • Fail-safe control
  • Integrated valve switches for purging gas input and output
  • 10 mm purging gas connection
  • Connection possibility of seperate pressure sensors

Certificates

German English DMT 99 ATEX E 082
English CSA 2654548
Korean KTL 13-KB4BO-0634
Russian GOST R POCC DE.ME92.B02732
Byelorussian GOSPROMNADZOR 11-02-0015-2012

Ex protection type

ATEX:
Ex II 2(1)G Ex e d ib [ia Ga px] IIC T4 Gb

Ambient temperature

Directive 2004/108/EC
Directive 94/9/EC

Description

The control unit APEX 2003.MV controls and monitors the purging and operating cycle of analysers with ?Containment Systems?

Additional function:
Due to the internal mounting of the purging circuit, the pressurised enclosure is constantly purged with a defined quantity of purging gas.

The purging gas flow rate during purging is 4100 NI/h max. The constant purging can be set from 0 to 6.0 l/min. 4 freely programmable relay outputs are available for the separation of data lines.

Technical data (extract)

(Click here for more information)
Protection classIP 65
StructureEx e protective enclosure with viewport lid
MaterialEnclosure material: glass-fiber reinforced, polyester
Purging time0 to 99 min; 5 sec. dropout delay
Weight11 kg
VoltageAC 230 V (AC 115 V) ?10%
PowerPv = 15 W/230 V
ConnectionTerminals 2.5 mm?, fine stranded

Documentation

Data Sheet - Ex p control unit APEX 2003.SI (Dilution) German English French Russian Spanish Portuguese Italian 
Declaration of Conformity 01-3711-7C0001 German English French 
Customer requirements - Ex p equipment German English French Russian Spanish Portuguese Italian 
Operating Instructions - Control Unit APEX 2003.SI German English French Russian Spanish Portuguese Italian