Ex p control unit APEX 2003.SI (High pressure)

07-3711-3223/.003

Features

  • 4 voltage free contacts
  • 3-line LCD display
  • LED status display
  • Modular design
  • Fail-safe control
  • Integrated valve switches for purging gas input and output
  • 10 mm purging gas connection
  • Connection possibility of seperate pressure sensors

Certificates

German English DMT 99 ATEX E 082
English CSA 2654548
Korean KTL 13-KB4BO-0634
Byelorussian GOSPROMNADZOR 11-02-0015-2012

Ex protection type

ATEX:
Ex II 2(1)G Ex e d ib [ia Ga px] IIC T4 Gb

Ambient temperature

Directive 2004/108/EC
Directive 94/9/EC

Description

The Ex p control unit APEX 2003.MV controls and monitors the purging and operating cycle of analysers with ?Containment Systems?.

Additional function:
By means of additional pressure sensors, a proportional valve adjusts the interior enclosure pressure to a value which is higher than that of the measuring gas. The purging gas flow rate during purging is 4100 NI/h at an interior enclosure pressure of 50 mbar.

4 freely programmable relay outputs and 8 contact assemblies are available for the separation of data lines.

Technical data (extract)

(Click here for more information)
Protection classIP 65
StructureEx e protective enclosure with viewport lid
Materialglass-fibre reinforced polyester
Purging time0 to 99 min; 5 sec. dropout delay
Weight11 kg
VoltageAC 230 V (AC 115 V) ?10%
PowerPv = 21 W/230 V
ConnectionTerminals 2.5 mm?, fine stranded

Documentation

Data Sheet - Ex p control unit APEX 2003.SI (High pressure) German English French Russian Spanish Portuguese Italian 
Declaration of Conformity 01-3711-7C0001 German English French 
Customer requirements - Ex p equipment German English French Russian Spanish Portuguese Italian 
Operating Instructions - Control Unit APEX 2003.SI German English French Russian Spanish Portuguese Italian