Ex p control unit APEX 2003.002x

07-3711-1216/...7

Features

  • 4 voltage free contacts
  • 3-line LCD display
  • LED status display
  • Modular design
  • Fail-safe control

Certificates

German English DMT 99 ATEX E 082
English IECEx BVS 13.0039
Chinese NEPSI GYJ13.1200
English CSA 2654548
Korean KTL 13-KB4BO-0634
Portuguese NCC 14.02972 X
Russian GOST R POCC DE.ME92.B02732
Byelorussian GOSPROMNADZOR 11-02-0015-2012

Ex protection type

ATEX:
Ex II 2(1)G Ex e d ib [ia Ga px] IIC T4/T6 Gb
Ex II 2(1)G Ex e d [ia Ga px] IIC T6 Gb
IECEx:
Ex e d ib [ia Ga px] IIC T4/T6 Gb
Ex e d [ia Ga px] IIC T6 Gb

Ambient temperature

Directive 2004/108/EC
Directive 94/9/EC

Description

The Ex p control unit APEX 2003.002x controls and monitors the purging and operating cycle of standard Ex p enclosures.

Purging gas input is via a digital valve up to NW 7.7 (74 m?/h) or a proportional valve up to NW 6 (45 m?/h).

The purge time is set at the control module via a turn switch, the setting of the pushbuttom values is via pushbutton or RS 485 interface. These control unit reduce the flushing time by half against the standard unit.

Technical data (extract)

(Click here for more information)
Protection classIP 65
Materialglass-fibre reinforced polyester
Purging time0 to 99 min; 5 sec. dropout delay
Weight7.5 kg
VoltageAC 230 V (AC 115 V) ?10%
PowerPv = 8 W/230 V
ConnectionTerminals 2.5 mm?, fine stranded

Documentation

Data Sheet - Ex p control unit APEX 2003.002x German English French Russian Spanish Italian 
Declaration of Conformity 01-3711-7C0001 German English French 
Customer requirements - Ex p equipment German English French Russian Spanish Portuguese Italian 
Operating instructions - Control unit APEX 2003, Type 07-3711-.2../.... German English French Russian Spanish Portuguese Italian