Flameproof control units EEx d IIB

EJB ...

Features

  • Standard components
  • Cost-effective; also applies to spare parts
  • Easy-to-service
  • Expandible

Certificates

English KEMA 08ATEX0123
English CESI 02 ATEX 097

Ex protection type

Ex II 2G Ex d...IIB, IIB+H2 T6, T4
Ex II 2(1, 2 or 3)G Ex d...IIB, IIB+H2 T6, T5
Ex II 2D Ex td...A21 IP6X T80 °C - T130 °C
Ex II 2(1, 2 or 3)D Ex tD...A21 IP6X T80 °C - T130 °C

Description

The BARTEC EEx d control panels are constructed according to protection type EEx d, flameproof encapsulation. Standard components such as switches, contactors and relays are mounted in an explosionproof enclosure constructed in such a way as to keep internal explosions from igniting the surrounding atmosphere.

EEx d control panels are usually custom-built in close cooperation with the customer himself for his special application.

Version:
Flameproof control panels are available either with direct cable-entries through EEx d cableglands or with indirect cable-entries through a junction box with protection type increased safety EEx e. The electrical wiring between EEx d and EEx e enclosure will be done through EEx d linebushings.

Technical data (extract)

(Click here for more information)
Protection classIP 65/IP 66/IP 67
MaterialAluminium aloy, low copper contents (standard)
Stainless steel 1.4401 (V4A) (option)
Stainless steel 1.4404 (A44A) (on request)
VoltageNominal voltage: AC 1000 V, DC 1500 V
Operating voltage: 25 kV
Current1000 A

Documentation

Data Sheet - Flameproof control units EEx d IIB German English French Russian 
Customer requirements - Flameproof control stations German English French Russian